output voltage: | |
---|---|
Availability: | |
Quantity: | |
ELC-AS/AL Series Switching Power Supply highlights at a glance:
◆EMI filter condenser
◆Input frequency:47~63HZ
◆Output voltage stability:0.5%
◆Can be used for DIN rail mounting (EN50022-35)
◆Wide range voltage input(100~240VAC/140~340VDC)
◆Ripple voltage tolerance range(85-264VAC/120-370VDC)
◆Output voltage fine adjustment range(-5% ~+10%),adjusting potentiometer V
◆Have the function of soft-start(to limit the peak current of start and the pressure of the voltage to the components)
◆The current of the load can be roughly adjusted (Means the maximum protective current of the load, adjusting
potentiometer A)
◆Effective:>75%
◆Insulation voltage endurance:>1.5KV
◆Power supply output with the LED indicator
◆Ripple:≤150mVp-p
◆Have the short circuit and over-load protection.(Short circuit protection means miss-connect the output voltage in short,
after disconnect, the output will be renew; Over-load protection: 105%-135%)
◆ With the UPS function. (External-connected battery, provide with the UPS by the power supply and the battery.)
◆With the remote control function. (By the switch control the having and non-having of the output voltage).
◆With the over-heat protection function.(The main control CMOS chip stops output when the temperature is beyond 135C
and the output will renew automatically when the temperature reduces.
ELC-AS/AL Series Switching Power Supply highlights at a glance:
◆EMI filter condenser
◆Input frequency:47~63HZ
◆Output voltage stability:0.5%
◆Can be used for DIN rail mounting (EN50022-35)
◆Wide range voltage input(100~240VAC/140~340VDC)
◆Ripple voltage tolerance range(85-264VAC/120-370VDC)
◆Output voltage fine adjustment range(-5% ~+10%),adjusting potentiometer V
◆Have the function of soft-start(to limit the peak current of start and the pressure of the voltage to the components)
◆The current of the load can be roughly adjusted (Means the maximum protective current of the load, adjusting
potentiometer A)
◆Effective:>75%
◆Insulation voltage endurance:>1.5KV
◆Power supply output with the LED indicator
◆Ripple:≤150mVp-p
◆Have the short circuit and over-load protection.(Short circuit protection means miss-connect the output voltage in short,
after disconnect, the output will be renew; Over-load protection: 105%-135%)
◆ With the UPS function. (External-connected battery, provide with the UPS by the power supply and the battery.)
◆With the remote control function. (By the switch control the having and non-having of the output voltage).
◆With the over-heat protection function.(The main control CMOS chip stops output when the temperature is beyond 135C
and the output will renew automatically when the temperature reduces.
ELC-AL Series Switching Power Supply | |||
Model | ELC-05AL | ELC-12AL | ELC-24AL |
Voltage(V) | DC5V | DC12V | DC24V |
Current(A) | 10A | 6A | 3A |
Dimensions(WxHxD) | 126mm*106mm*65mm | ||
Installation | Standard 35mm DIN (EN50022-35) | ||
Gamut voltage | 100-240VAC/140-340VDC | ||
Ripple voltage tolerance range | 85-264VAC/120-370VDC | ||
Input frequency | 47-63HZ | ||
Out voltage stability | ≤±0.5% | ||
Ripple | ≤150mVp-p | ||
Operation Temperature | -25℃ to +70℃ | ||
Efficiency | >80% |
ELC-AL Series Switching Power Supply | |||
Model | ELC-05AL | ELC-12AL | ELC-24AL |
Voltage(V) | DC5V | DC12V | DC24V |
Current(A) | 10A | 6A | 3A |
Dimensions(WxHxD) | 126mm*106mm*65mm | ||
Installation | Standard 35mm DIN (EN50022-35) | ||
Gamut voltage | 100-240VAC/140-340VDC | ||
Ripple voltage tolerance range | 85-264VAC/120-370VDC | ||
Input frequency | 47-63HZ | ||
Out voltage stability | ≤±0.5% | ||
Ripple | ≤150mVp-p | ||
Operation Temperature | -25℃ to +70℃ | ||
Efficiency | >80% |
Installation Dimensions :
(unit:mm)
Using Methods:(Taking ELC-24AL as example)
General operation:
Fig.3.1 General application
Operation Step:
1.Twist firmly the short-circuit block of the switch terminal. (If the switch or the short-circuit is off, the switch power
have no output).
2.Adjusting potentiometer (A) and rotate it to the end clockwise.
3.Connect the power(100-240VAC/140-340VDC)
4.Adjusting potentiometer(V) to make the voltage of the output terminal is +-24VDC
5.Connect the load in the output terminal (Pay attention to the straight polarity and negative polarity and the maximum
working current must be<=3A.)
2.Remote control
Attn: Externally-Connect the switch terminal, remote the switch to control output voltage having or non-having.
Operation step:
Remove the short circuit block from the switch terminal and replace it with a switch K1
Adjusting potentiometer (A) and rotate it to the clockwise.
Connect the power(100-240V/140-340VDC)
Adjusting potentiometer(V) to make the output terminal voltage is +-24VDC(Close the switch K1)
Load(Working current <=3A)
Close the switch K1, no voltage output.
Fig 3.2 Remote control application
3.Using UPS function:
Attn:If the load can provide with UPS voltage methods, then you can use this function.
(Attn: the connection of the positive and negative pole)
Operation Step:
1.Twist firmly the short circuit block of the switch terminal.(If the switch short-circuit block is off, the switch can not
output)
2.Adjusting potentiometer (A) and rotate it to the end of the clockwise.
3.Connect the power(100-240VAC/140-340VDC)
4.Adjusting potentiometer (V) to make the output voltage is +24VDC(Due to ELC-12AS/AL to make the output voltage
is 12V)
5.Disconnect the AC/DC power wire.
6.Connect the switch and fuse wire and the battery according to the positive pole and the negative pole marked on the
crust.
7.Connect the power(100-240VAC/140-340VDC)( If the battery voltage is over +24V, you need to adjust potentiometer
(V) to make it over battery voltage)
Attn: 1). At this time the main output voltage is provided by load; BATT port charges the accumulator battery by the
switch K2 and fuse wire F1; If there is no AC/DC voltage input, battery power supply the load by the internal
circuit, the Maximum working current <=3A.
2).At this time the main output voltage provided by load is more 24V.
4.Using Remote control and UPS simultaneously
Attn: Using remote control and UPS simultaneously, the using method is combined by the method 2 and the method 3
as below:
(Attn:the connection of the positive an negative pole)
(Fig3.4 Using remote control and UPS simultaneously application)
Installation Dimensions :
(unit:mm)
Using Methods:(Taking ELC-24AL as example)
General operation:
Fig.3.1 General application
Operation Step:
1.Twist firmly the short-circuit block of the switch terminal. (If the switch or the short-circuit is off, the switch power
have no output).
2.Adjusting potentiometer (A) and rotate it to the end clockwise.
3.Connect the power(100-240VAC/140-340VDC)
4.Adjusting potentiometer(V) to make the voltage of the output terminal is +-24VDC
5.Connect the load in the output terminal (Pay attention to the straight polarity and negative polarity and the maximum
working current must be<=3A.)
2.Remote control
Attn: Externally-Connect the switch terminal, remote the switch to control output voltage having or non-having.
Operation step:
Remove the short circuit block from the switch terminal and replace it with a switch K1
Adjusting potentiometer (A) and rotate it to the clockwise.
Connect the power(100-240V/140-340VDC)
Adjusting potentiometer(V) to make the output terminal voltage is +-24VDC(Close the switch K1)
Load(Working current <=3A)
Close the switch K1, no voltage output.
Fig 3.2 Remote control application
3.Using UPS function:
Attn:If the load can provide with UPS voltage methods, then you can use this function.
(Attn: the connection of the positive and negative pole)
Operation Step:
1.Twist firmly the short circuit block of the switch terminal.(If the switch short-circuit block is off, the switch can not
output)
2.Adjusting potentiometer (A) and rotate it to the end of the clockwise.
3.Connect the power(100-240VAC/140-340VDC)
4.Adjusting potentiometer (V) to make the output voltage is +24VDC(Due to ELC-12AS/AL to make the output voltage
is 12V)
5.Disconnect the AC/DC power wire.
6.Connect the switch and fuse wire and the battery according to the positive pole and the negative pole marked on the
crust.
7.Connect the power(100-240VAC/140-340VDC)( If the battery voltage is over +24V, you need to adjust potentiometer
(V) to make it over battery voltage)
Attn: 1). At this time the main output voltage is provided by load; BATT port charges the accumulator battery by the
switch K2 and fuse wire F1; If there is no AC/DC voltage input, battery power supply the load by the internal
circuit, the Maximum working current <=3A.
2).At this time the main output voltage provided by load is more 24V.
4.Using Remote control and UPS simultaneously
Attn: Using remote control and UPS simultaneously, the using method is combined by the method 2 and the method 3
as below:
(Attn:the connection of the positive an negative pole)
(Fig3.4 Using remote control and UPS simultaneously application)
ELC-AL Series Switching Power Supply | ||||
Model | Voltage(V) | Current(A) | Gamut voltage | Gross Weight(G) |
ELC-05AL | DC5V | 10A | 100-240VAC/140-340VDC | 500 |
ELC-12AL | DC12V | 6A | 100-240VAC/140-340VDC | 500 |
ELC-24AL | DC24V | 3A | 100-240VAC/140-340VDC | 500 |
ELC-AL Series Switching Power Supply | ||||
Model | Voltage(V) | Current(A) | Gamut voltage | Gross Weight(G) |
ELC-05AL | DC5V | 10A | 100-240VAC/140-340VDC | 500 |
ELC-12AL | DC12V | 6A | 100-240VAC/140-340VDC | 500 |
ELC-24AL | DC24V | 3A | 100-240VAC/140-340VDC | 500 |